Description
Ctec EP203 Automatic Extinguisher Panel
LPCB certified to EN 12094-1 (the European standard for Fixed Firefighting Systems – Components for Gas Extinguishing Systems) and EN54-2/4, the EP203 three-zone automatic extinguisher panel epitomizes quality, durability, and reliability.
Specifically designed for use in areas housing expensive, dangerous or irreplaceable items of equipment, it features an intuitive 128 x 64-pixel display that gives clear and concise feedback to the user, installer, and commissioning engineer. It has six monitored inputs (including hold & abort), a time-stamped log, adjustable flood times, and volt-free changeover relays for fire, local fire, 1st stage active, 2nd stage active, extractor fan, and fault.
All of the panel’s electronics – apart from its powerful 3A EN54-4 switch mode PSU – are mounted on a detachable metal bridge plate for ease of installation. A wide range of ancillaries is also available including remote status units, hold-off & abort buttons, line terminators, and relay boards.
Technical Specification
Approvals/certifications | Certified to EN12094-1 and EN54-2 & 4 by the LPCB. |
Mains supply | 230V 50/60Hz. |
Mains rated current | 810mA max. |
Internal power supply | 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault). |
Total output current limited to | 1.5A @ 230Vac continuous, 3A peak (ImaxA eq 800mA). |
Quiescent current | 40mA (on mains fail). Zone quiescent 2mA max. |
Max battery size and type | 2 x 12V 7Ah VRLA connected in series. |
No. of detector zone circuits | 3 @ 19-28Vdc (Max. length per circuit is 250m). |
Max. devices per detector zone | 20 detectors (or 32 detectors/manual call points combined). |
No. of conventional sounder circuits | 3 (two x 1st stage; one x 2nd stage). Max. length per circuit is 50m). |
EOL resistor value | 6800Ω 5% Tol. 0/25W (blue, grey, red, gold). |
Max. sounder output current | 3 x 200mA. |
Auxiliary relays | Six: (1) Fire; (2) Local Fire; (3) Extract Fan; (4) 1st Stage; (5) 2nd Stage; (6) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc. Five additional relays available via EP212 relay card. |
Other outputs | Extinguishant release (21-28Vdc, rated at 1A for 5 mins). Programmable to delay by 0-60 seconds; to be active for 1-300 seconds and to flood for 60-1800 seconds. |
Auxiliary inputs | Six: (1) Manual Release; (2) Flow Switch; (3) Low Pressure; (4) Mode; (5) Hold; (6) Abort. 8K-2KΩ normal; 1.8K-200Ω active; 150-0Ω short circuit. EOL value: 6K8 +/-5%, 0.25W. |
Indicators | Multiple indicators are provided – refer to the EP203 instructions for details. |
Controls | Extinguishant release (housed in yellow casing); Accessed keyswitch; Operation keyswitch (Manual only or Manual & Auto); Buttons for Menu; Silence internal sounder; reset panel; silence/resound sounders and scrolling. |
Expansion connections | Yes – for up to 8 x Remote status units (2 wire RS485 + 2 wire power) and/or up to 8 x Ecomomy status units (2 wire power + 2 wire mode select). |
Product dimensions (mm) | 439 W x 276 H x 70 D mm (back box); 467 W x 293 H x 29 D mm (lid). |
Construction & finish | Metal back box; metal chassis’ plastic lid. |
IP Rating | IP30. |
Weight | 4.2kg (without batteries). |
Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95%. |
https://Www.Waste-Ndc.pro/community/profile/tressa79906983/ –
Woah! I’m really loving the template/theme of this website.
It’s simple, yet effective. A lot of times it’s tough to get that “perfect balance” between superb usability and appearance.
I must say that you’ve done a very good job with this.
Additionally, the blog loads very quick for mme on Safari.
Superb Blog! https://Www.Waste-Ndc.pro/community/profile/tressa79906983/