Asenware AW-CFP2166 16 Zone Conventional Fire Panel
The AW-CFP2166 series 8 Zone conventional fire alarm panel is designed based on EN54 part 2&4 standard. And it is the central part of conventional fire alarm system, designed for applications requiring smoke detector, bell, manual pull stations, and sprinkler supervision. Each zone can be disabled by a button. The basic unit offers 1 to 8 zones of initiation, up to 16 zones for larger applications.
Mains supply voltage | 110VAC or 220VAC |
Internal power supply | 27.2VDC |
Total output current limited | 3A @ 220VAC |
Batteries (default configuration) | 12V2.3AH*2 |
Number of circuit | 12-32 |
End of Line device | 6.8k Ω,5% tolerance, 0.5-1W (colour code-blue,grey,red,gold) |
Call point resistor value | 470 to 680 Ω, 0.5 or 1 watt |
Number of general circuits | 2 |
Outputs fused AT | 600mA |
Maximum number of bells @ 50mA of each Sounder output | 30 |
Battery fuse | 1.85A resettable fuse |
Sounder outputs | 750mA resettable fuse |
Output type | NC and NO relay |
Maximum current | 100mA |
Largest acceptable conductor size | 2.5mm2 |
Smallest acceptable conductor size | 0.75mm2 |
Dimensions(mm) | 640X390X150 |
Weight (with batteries) | 13kg |