Description
Zeta Addressable Heat Detector
The Fyreye MKII Rate of Rise heat detector (MKII-AHR) uses a thermistor arrangement to
sense a quick rise in temperature and also a final threshold temperature of 57°C. The Fyreye
fixed heat detector (MKII-AHF) has a single thermistor arrangement that gives an alarm at
a temperature of 57°C, where the MKII-AHF/CS90 gives an alarm above 86°C.
Technical Specifications:
Model |
MKII-AHF |
MKII-AHF/B |
MKII-AHF/CS90 |
MKII-AHF/CS90/B |
MKII-AHR |
MKII-AHR/B |
|
Part No. |
80-214 |
80-214/B |
80-218 |
80-218/B |
80-212 |
80-212/B |
|
Detector Class |
Fixed Heat Only A2S |
Fixed Heat Only CS |
Rate of Rise & Fixed Heat Detector A1R |
||||
Design Standard |
EN54 part 5 |
EN54 part 5 |
EN54 part 5 |
||||
Approval |
LPCB |
||||||
Operating Voltage |
17 to 28V DC |
||||||
Quiescent Current |
500μA |
||||||
Alarm Current @ 24Vdc |
5mA |
||||||
Operating Temp. (°C) |
-10 to +50°C |
-10 to +80°C |
-10 to +50°C |
||||
Min. Continuous Temp. |
0°C |
||||||
Max. Humidity |
95% RH non-condensing |
||||||
Alarm Condition |
Fixed heat trigger @ 57°C |
Fixed heat trigger @ 90°C |
Rate of rise or fixed heat trigger @ 57°C |
||||
Coverage |
50m² |
50m² |
50m² |
||||
IP Rating |
IP43 |
||||||
Start-up Time |
10 Seconds |
||||||
Size (with Base) |
100 x 49 mm |
100 x 49 mm |
100 x 49 mm |
||||
Weight (with Base) |
75g (133g) |
||||||
Remote Output |
5mA at 24VDC |
Reviews
There are no reviews yet.